Main circuit terminal specification
Cable size, crimp terminal size
Select a recommended gauge size cable to ensure that the voltage drop ratio is within 2%.
The following indicates selection examples when the wiring length from the power supply to the converter is 20 m.
Common bus regeneration mode with harmonic suppression disabled
MCCB MC
Power
supply
• 200 V class
Model
Rating
50°C
FR-XC-7.5K
40°C
50°C
FR-XC-11K
40°C
50°C
FR-XC-15K
40°C
FR-XC-22K
50°C
FR-XC-18.5K-PWM
40°C
FR-XC-30K
50°C
FR-XC-22K-PWM
40°C
FR-XC-37K
50°C
FR-XC-37K-PWM
40°C
FR-XC-55K
50°C
FR-XC-55K-PWM
40°C
Model
Rating
50°C
FR-XC-7.5K
40°C
50°C
FR-XC-11K
40°C
50°C
FR-XC-15K
40°C
FR-XC-22K
50°C
FR-XC-18.5K-PWM
40°C
FR-XC-30K
50°C
FR-XC-22K-PWM
40°C
FR-XC-37K
50°C
FR-XC-37K-PWM
40°C
FR-XC-55K
50°C
FR-XC-55K-PWM
40°C
∗1
It is the gauge of a cable with the continuous maximum permissible temperature of 75°C (HIV cable (600 V grade heat-resistant PVC insulated
wire), etc.). It assumes a surrounding air temperature of 50°C or less (40°C or less for the 40°C rating) and the wiring distance of 20 m or less
from the power supply to the converter.
∗2
The cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C. It assumes a surrounding air temperature
of 40°C or less and the wiring distance of 20 m or less from the power supply to the converter.
(For the use in the United States or Canada, refer to
44
INSTALLATION AND WIRING
b: FR-XCL to FR-XC
a: Power supply to
FR-XCL
FR-XCL
Fuse
R/L1
R2/L12
S/L2
S2/L22
Fuse
T/L3
T2/L32
Fuse
d: Power supply to FR-XC
Crimp terminal (for HIV cables, etc.)
R, S, T
R2, S2, T2
P, N
8-5
1.25-4
8-6
5.5-5
1.25-4
14-5
14-6
1.25-4
22-5
22-6
1.25-4
38-8
38-6
1.25-4
60-8
60-6
1.25-4
80-10
80-10
1.25-4
100-10
100-10
2
HIV cables, etc. (mm
Location in the
connection diagram
a, b
c
d
∗4
8
8
1.25
5.5
14
14
1.25
22
22
1.25
38
38
1.25
60
60
1.25
80
80
1.25
100
100
1.25
page
FR-XC
P4
R2/L12
Fuse
S2/L22
P/+
T2/L23
Fuse
N/-
R/L1
S/L2
T/L3
R1/L11
c: FR-XC to inverter
S1/L21
Earth
R1, S1
(ground)
5.5-4
1.25-4
5.5-4
8-5
1.25-4
8-5
1.25-4
14-5
1.25-4
22-6
1.25-4
22-6
1.25-4
22-8
1.25-4
22-8
Cable gauge
AWG/MCM
)
∗2
∗1
Location in the
Earth
connection diagram
(ground)
a, b
c
5.5
8
8
8
6
6
14
4
4
22
2
2
1
22
1/0
1/0
2/0
22
2/0
3/0
38
4/0
4/0
179.)
Inverter
R/L1
S/L2
T/L3
R1/L11
S1/L21
IM
M
P/+
N/-
Crimp terminal
(for HIV cables, etc.)
Model
Rating
R, S, T, R2, S2, T2
50°C
FR-XCL-7.5K
40°C
50°C
FR-XCL-11K
40°C
50°C
FR-XCL-15K
40°C
50°C
FR-XCL-22K
40°C
50°C
FR-XCL-30K
40°C
50°C
FR-XCL-37K
40°C
50°C
FR-XCL-55K
40°C
PVC cables, etc. (mm
Location in the
connection diagram
d
a, b
c
d
16
10
10
1.5
16
10
16
1.5
16
16
25
1.5
16
25
25
1.5
16
35
50
1.5
16
50
70
1.5
16
95
95
1.5
8-5
5.5-5
14-5
22-6
38-6
60-6
80-10
100-10
2
)
∗3
Earth
(ground)
10
16
16
16
25
35
50