Installation of reactor (FR-XCL)
Clearances
Because the reactor generate heat, leave sufficient space around them.
10 cm or more
5 cm or more
5 cm or more
Installation place
Install the reactor on nonflammable material. Installing it directly on flammable material will cause a fire.
Surrounding environment
Avoid places where the equipment is subjected to oil mist, flammable gases, fluff, dust, dirt, etc.
Install the equipment in a clean place or protect it from suspended substances.
Installation orientation
To prevent looseness, install the reactor on a horizontal surface securely with screws or bolts.
Do not install it on a vertical surface. Install it on a mounting stand which can withstand its weight.
NOTE
• Since the charged section of the reactor is uncovered, fully protect it to prevent ground fault and electric shock.