Vibration, impact
The vibration resistance of the multifunction regeneration converter is up to 5.9 m/s
amplitude for the directions of X, Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and
cause poor contacts of connectors, even if those vibration and impacts are within the specified values.
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Measures
• Provide the enclosure with rubber vibration isolators.
• Strengthen the structure to prevent the enclosure from resonance.
• Install the enclosure away from the sources of the vibration.
2.3.2

Cooling system types for converter enclosure

From the enclosure that contains the multifunction regeneration converter, the heat of the converter and other equipment
(inverter, transformers, reactors, lamps, resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to
keep the in-enclosure temperature lower than the permissible temperatures of the in-enclosure equipment including the
converter.
The cooling systems are classified as follows in terms of the cooling calculation method.
(a) Cooling by natural heat dissipation from the enclosure surface (totally enclosed type)
(b) Cooling by heatsink (aluminum fin, etc.)
(c) Cooling by ventilation (forced ventilation type, pipe ventilation type)
(d) Cooling by heat exchanger or cooler (heat pipe, cooler, etc.)
Cooling system
Natural ventilation
(enclosed ventilated type)
Natural
Natural ventilation (totally
enclosed type)
Heatsink cooling
Forced ventilation
Forced air
Heat pipe
Installation of the converter and enclosure design
Enclosure structure
FR-XC
FR-XC
Heatsink
FR-XC
FR-XC
Heat pipe
FR-XC
2
at 10 to 55 Hz frequency and 1 mm
Comment
This system is low in cost and generally used, but the
enclosure size increases as the converter capacity increases.
This system is for relatively small capacities.
Being a totally enclosed type, this system is the most
appropriate for hostile environment having dust, dirt, oil mist,
etc. The enclosure size increases depending on the converter
capacity.
This system has restrictions on the heatsink mounting position
and area. This system is for relatively small capacities.
This system is for general indoor installation. This is
appropriate for enclosure downsizing and cost reduction, and
often used.
This is a totally enclosed for enclosure downsizing.