Rating
6.1.2

FR-XC-[ ]K-PWM

200 V class
Model FR-XC-[ ]K-PWM
Applicable inverter
capacity (kW)
Applicable motor
current (A)
Rated input current (A)
Overload current rating
Power supply capacity
(kVA)
∗3
Applicable inverter
capacity (kW)
Applicable motor
current (A)
Rated input current (A)
Overload current rating
Power supply capacity
(kVA)
∗3
Potential regenerative capacity (kW)
Rated current (A) (regenerative driving)
Overload current rating
Potential regenerative capacity (kW)
Rated current (A) (regenerative driving)
Overload current rating
Rated input AC voltage/
frequency
Permissible AC voltage
fluctuation
Permissible frequency
fluctuation
Input power factor
Protection rating of structure (IEC 60529)
Cooling system
Number of connectable inverters
Approx. mass (kg)
∗7
∗1
The harmonic suppression function in this model is enabled initially.
∗2
The converter with its harmonic suppression function disabled can be set in the power regeneration mode.
∗3
Selection example for 220 V power supply voltage.
∗4
IP20 for the FR-XCB.
∗5
The DC bus voltage is approx. 297 VDC at an input voltage of 200 VAC, approx. 327 VDC at 220 VAC, and approx. 342 VDC at 230 VAC.
∗6
One inverter for operation in the power regeneration mode.
∗7
Mass of the FR-XC alone.
∗8
Maximum capacity of regenerative power generated from the Mitsubishi Electric 4-pole standard motor in each axis.
158
SPECIFICATIONS
∗1
Harmonic suppression
Disabled
Enabled
Disabled
Enabled
Power
driving
Disabled
Regenerative
driving
Power/
Enabled
regenerative
(HS)
driving
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Power
driving
Disabled
Regenerative
driving
Power/
Enabled
regenerative
(HS)
driving
Disabled
Enabled
∗8
∗8
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Enabled
18.5
22
22
30
18.5
22
90
115
76
90
92
124
74
102
69
82
100% continuous / 150% 60 s
41
52
30
35
22
30
18.5
22
99
127
83
99
101
136
81
112
75
90
100% continuous / 150% 60 s
45
57
32
38
18.5
22
62
74
100% continuous / 150% 60 s
18.5
22
68
81
100% continuous / 150% 60 s
Three-phase 200 to 240 V, 50/60 Hz
Three-phase 200 to 230 V, 50/60 Hz
Three-phase 170 to 264 V, 50/60 Hz
Three-phase 170 to 253 V, 50/60 Hz
±5%
±5%
0.99 or more (when load ratio is 100%)
Open type (IP00)
Forced air
10
∗6
10.5
10.5
37
55
37
55
37
55
145
215
145
215
151
223
125
186
134
198
66
100
57
84
37
55
37
55
160
236
160
236
166
245
138
204
147
217
73
110
62
92
30
45
102
152
30
45
112
167
∗5
∗4
28
38