Dedicated box-type reactor (option) model
FR-XCB-
H
K-
Symbol
Voltage class
Reactor capacity
None
200 V class
Capacity (kW)
H
400 V class
How to read the SERIAL number
Rating plate example
Symbol Year
Month Control number
SERIAL
Accessory
• Earthing (grounding) cable (1)
For connection with a communication option. (Refer to
• Communication option LED label (1)
For checking the LED indications on the communication option. (Refer to
1.1.4
Harmonic suppression guidelines in Japan
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The Harmonic Suppression
Guidelines was established to protect other consumers from these outgoing harmonic currents.
All capacity and all models of general-purpose inverter used by specific consumers are now covered by "the Harmonic
Suppression Guidelines for Consumers Who Receive High Voltage or Special High Voltage" (hereinafter referred to as
"the Specific Consumer Guidelines").
"Specific Consumer Guidelines"
This guideline sets forth the maximum harmonic currents outgoing from a high-voltage or especially high-voltage receiving
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
• Maximum values of outgoing harmonic currents per 1 kW contract power
Received
power
5th
voltage
6.6 kV
3.5
22 kV
1.8
33 kV
1.2
Symbol Circuit board coating
None
Without
60
With
The SERIAL consists of one symbol, two characters indicating the
production year and month, and six characters indicating the control number.
The last digit of the production year is indicated as the Year, and the Month is
indicated by 1 to 9, X (October), Y (November), or Z (December).
7th
11th
2.5
1.6
1.3
0.82
0.86
0.55
page
71.)
page
71.)
13th
17th
1.3
1.0
0.69
0.53
0.46
0.35
Pre-operation instructions
19th
23rd
Over 23rd
0.9
0.76
0.70
0.47
0.39
0.36
0.32
0.26
0.24
OUTLINE
1
11