 Mount point change of installation frame from the rear to the front
The upper and lower installation frames are attached on the multifunction regeneration converter (one for each position).
Change the mount point of the upper and lower installation frames from the rear to the front as shown in the figure.
When reattaching the installation frames, make sure that the installation orientation is correct.
 Installation of the multifunction regeneration converter on the enclosure
Push the multifunction regeneration converter heat sink part outside the enclosure, and fix the multifunction regeneration
converter to the panel with upper and lower installation frames.
Enclosure
Inside the
enclosure
10 mm ∗2
Exhausted air
Converter
Installation
Cooling
wind
∗1
NOTE
• As the heat sink part protruded through the panel includes a cooling fan, this type of installation is not suitable for the
environment of water drops, oil, mist, dust, etc.
• Be careful not to drop screws, dust etc. into the multifunction regeneration converter and cooling fan section.
Installation of the converter and enclosure design
Shift
Shift
frame
∗1
Dimension of the outside of the enclosure
Multifunction regeneration
FR-XC-(H)37K, FR-XC-H55K
FR-XC-(H)37K-PWM, FR-XC-H55K-PWM
FR-XC-55K
FR-XC-55K-PWM
∗2
To avoid interference with the cooling fan on top of the heatsink, the thickness of the rear
panel of the enclosure should not exceed 10 mm and the space around the fan should be
cleared.
Upper
installation
frame
Lower
installation
frame
converter
INSTALLATION AND WIRING
Dimension of the
outside of the
enclosure (mm)
105
135
35
2

Hide quick links: