Check first when you have a trouble

Clearing the fault history
POINT
POINT
• Set Err.CL Fault history clear = "1" to clear the fault history.
Turning ON the power of the converter
1.
The operation panel is in the monitor mode.
Selecting the parameter setting mode
2.
Press
to choose the parameter setting mode. (The parameter number read previously appears.)
Selecting the parameter number
3.
Turn
until "
appears.
Fault history clear
Turn
to change the set value to "
"
" and "
4.
4.6
Check first when you have a trouble
Condition
The converter does not operate properly.
The operation status 7-segment LED
display does not come on.
The charge lamp on the converter does not
come on.
The inverter does not run.
A breaker trips.
Unusual noises are generated from the reactor.
144
PROTECTIVE FUNCTIONS
Operating procedure
" (Fault history clear) appears. Press
". Press
" are displayed alternately after the fault history is cleared.
•Turn
to read another parameter.
•Press
to show the setting again.
•Press
twice to show the next parameter.
Check the following about connection:
● Wiring is performed correctly.
● Appropriate power supply voltage is applied.
● The phase sequence is correct.
When the phase sequence is correct, check for the short circuit across terminals
SOF and SD and across terminals RES and SD.
Check the following about connection:
● Connection is performed correctly.
● Wiring for the main circuit terminals R/L1, S/L2, and T/L3 on the inverter is performed
correctly.
● The inrush current limit resistor is not damaged.
Check the following about connection:
● Connection is performed correctly.
● Wiring for the main circuit terminals R2/L12, S2/L22, and T2/L32 on the converter is
performed correctly.
Check the following about the setting:
● The parameter settings in the inverter are appropriate. (Setting method differs by the
inverter series.)
Check the following about connection:
● Wiring is performed correctly.
● Appropriate power supply voltage is applied.
● The phase sequence is correct.
Identify the cause of the trip and remove it before turning ON the power of the breaker.
It is not a fault if noise comes from the dedicated reactor during regenerative driving of the
converter (in other words, it is a fault if noise comes despite the stop state of the converter
by the Converter stop (SOF) signal).
If needed, devise methods of reducing noise by modifying the enclosure in which the
reactor is installed.
to read the present set value. "
to start clear.
Point to be checked