Current Control - Mitsubishi Electric FR-XC-18.5K-PWM Instruction Manual

Fr-xc series multifunction regeneration converter
Table of Contents

Advertisement

Parameter details
3.5.18
Current control (Pr.82 and Pr.83)
Use this function to control current output from the converter with harmonic suppression enabled as commanded.
Operation can be stable enough with these parameters in the initial setting, however, some adjustments may be required if
current vibration occurs depending on the power supply condition.
Pr.
Current control proportional
82
gain
83
Current control integral gain
• Adjust the fluctuation range of current by setting Pr.82.
Increasing the setting value reduces the current fluctuation caused by external disturbance.
• Adjust the recovery time to the commanded current after a current fluctuation by setting Pr.83.
Increasing the setting value shortens the recovery time from the current fluctuation caused by external disturbance.
NOTE
• Setting Pr.82 too large makes the operation unstable.
• Setting only Pr.83 makes the operation unstable.
102
PARAMETERS
Name
Initial value
100%
100%
Setting range
Set the proportional gain for the current
control.
0 to 200%
Increasing the setting value reduces the
current fluctuation caused by external
disturbance.
Set the integral gain for the current control.
Increasing the setting value shortens the
0 to 200%
recovery time from the current fluctuation
caused by external disturbance.
Description