EMC Directive
compliant
FSB-30-324
noise filter
• Connect the converter to an earthed (grounded) power supply.
• Install a motor and a control cable written in the Technical News (MF-S-135) according to the instruction.
• Confirm that the final integrated system with the converter conforms with the EMC Directive.
Low Voltage Directive
We have self-confirmed our multifunction regeneration converters as products compliant to the Low Voltage Directive
(Conforming standard EN 61800-5-1) and affix the CE marking on the converters.
 Outline of instructions
• Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.
Connect the equipment to the earth (ground) securely.
• Wire the earth terminal independently. (Do not connect two or more cables to one terminal.)
• Use the cable sizes on
page 43
• Surrounding air temperature: 40°C maximum
If conditions are different from above, select appropriate wire according to EN 60204.
• Use a tinned (plating should not include zinc) crimping terminal to connect the earth (ground) cable. When tightening the
screw, be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable whose size is indicated on
• Use the molded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
• DC current may flow from the converter to a protective earth (ground) conductor. When using a residual current device
(RCD) or residual current monitor (RCM), connect a type B RCD or RCM to the power supply side.
• Use the converter under the conditions of overvoltage category III (usable regardless of the earth (ground) condition of the
power supply), overvoltage category III (usable with the earth-neutral system power supply, 400 V class only) and pollution
degree 2 or lower specified in IEC60664.
• To use the converter under the conditions of pollution degree 2, install it in the enclosure of IP2X or higher.
• To use the converter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• On the input and output of the converter, use cables of the type and size set forth in EN 60204 Appendix C.
• The operating capacity of the relay outputs (terminal symbols A, B, and C) should be 30 VDC, 0.3 A. (Relay output has
basic isolation from the converter internal circuit.)
• Control circuit terminals on
• Environment
Surrounding air
-10 to +50°C
temperature
Ambient humidity
95% RH or less
Maximum altitude
2500 m
∗1
-10 to +40°C (non-freezing) at the +40°C rating.
∗2
For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
For the details, refer to the Technical News (MF-S-135).
FR-XC-H15K
FTB-80-663-L
under the following conditions.
page 57
are safely isolated from the main circuit.
During
In storage
operation
-20 to +65°C
∗1
95% RH or less
2500 m
∗2
FR-XC-H22K
FR-XC-H30K
FR-XC-H18.5K-PWM
FR-XC-H22K-PWM
Harmonic suppression
Disabled
Enabled
FTB-80-663-L
FTB-80-355-L
During
transportation
-20 to +65°C
95% RH or less
10000 m
FR-XC-H37K
FR-XC-H55K
FR-XC-H37K-PWM
FR-XC-H55K-PWM
Harmonic suppression
Disabled
Enabled
FTB-150-355-L
FTB-150-355-L
page
43.
APPENDIX
177