3.5.11

Function selection for monitor item indication

(Pr.46 to Pr.48, Pr.52, and Pr.896)
The monitor item to be displayed on the operation panel or the main monitor of the parameter unit can be selected.
Pr.
Name
46
Watt-hour meter clear
Energization time carrying-
47
over times
Cumulative power monitor
48
digit shifted times
52
PU main monitor selection
896
Power unit cost
Monitor items list (Pr.52)
• Use Pr.52 PU main monitor selection to select the item to monitor on the operation panel or the parameter unit.
• Refer to the following table and select the item to be monitored.
Increment
Monitor item
and unit
Input current
0.01 A
Input voltage
0.1 V
Bus voltage
0.1 V
Fault indication
Power supply
0.01 Hz
frequency
Electronic
thermal O/L relay
0.1%
load factor
Input power
0.01 kW
Cumulative
0.01 kWh
power
Cumulative
1 h
energization time
∗1
Input power with
regenerative
0.01 kW
driving indication
I/O terminal
status
Electricity cost
∗1
The cumulative energization time is accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
∗2
The currents value may be displayed due to undesirable current while the converter in the power regeneration mode is during power driving.
This is not a fault.
Initial value
9999
0
9999
0
0
Pr.52 setting
0
The input current to the converter is monitored.
0
The effective value of input voltage to the converter is monitored.
0
The output current from the converter is monitored.
Each of the last 8 faults is displayed individually.
5
The power supply frequency is monitored.
The motor thermal cumulative value displayed as a percentage with 100
6
being the thermal O/L relay operating level is monitored.
7
The input power to the converter is monitored.
The counter of cumulative power calculated from the input power monitor
8
value is displayed.
Use Pr.46 to clear the counter.
The counter of cumulative energization time since the converter shipment is
displayed.
9
The number of times a cumulative value has reached the maximum value of
65535 hours can be checked with Pr.47.
The values of input power during regenerative driving is displayed with signed
numbers on the operation panel. The monitoring on the parameter unit or via
10
communication does not support the display of the values with signed
numbers (the absolute values are displayed).
The ON/OFF status of I/O terminals on the multifunction regeneration
25
converter is displayed. The parameter unit does not support this display.
The electricity cost calculated from the electricity rate (cost per kWh) set in
28
Pr.896 and the cumulative energy is displayed.
Setting range
0
Set "0" to clear the watt-hour meter.
Set "10" to monitor the cumulative power
10
in the range of 0 to 9999 kWh via
communication.
Set "9999" to monitor the cumulative
9999
power in the range of 0 to 65535 kWh via
communication.
The number of times that the cumulative
0 to 65535
energization time exceeded 65535 hours
(Read-only)
is displayed Read-only.
Set the number of places the decimal
point on the watt-hour meter is shifted to
0 to 4
left.
The meter stops at the maximum number.
Shifting disabled.
9999
The meter is reset to 0 when it reaches the
maximum number.
Select the item monitored on the operation
panel or parameter unit.
0, 5 to 10, 25, 28
Refer to the following table for the monitor
item selection.
0 to 500
Set the electricity rate (cost per kWh).
Description
Parameter details
Description
∗2
95
PARAMETERS
3