Mitsubishi Electric FR-XC-18.5K-PWM Instruction Manual page 64

Fr-xc series multifunction regeneration converter
Table of Contents

Advertisement

Wiring between the power supply and the converter
Supply power to the power detecting terminals (R/L1, S/L2, and T/L3) separately from the main circuit wiring.
AC reactor
(FR-HAL)
R
X
S
Y
Power
supply
T
Z
MCCB
Cable gauge
1.25 mm
Total wiring length
10 m or shorter
NOTE
• The terminals R/L1, S/L2, and T/L3 on the converter are control terminals to detect power phases of the power supply. For
wiring, the voltage phase must be consistent between terminals R2/L12, S2/L22, and T2/L32 and terminals R/L1, S/L2, and
T/L3. If these terminals are not connected correctly, the converter does not operate properly.
• If the inverter is operated while the converter terminals R/L1, S/L2, and T/L3 are not connected to the power supply, the
converter will be damaged.
To the inverter
FR-XC
Dedicated reactor
(FR-XCL)
R/L1
R2/L12
R2/L12
S/L2
S2/L22
S2/L22
T/L3
T2/L32
T2/L32
R/L1
S/L2
T/L3
2
R1/L11
S1/L21
Jumper
INSTALLATION AND WIRING
Wiring
2
63