CLI User Guide
Where id is the ID for the chosen alarm.
3.
Configure the following parameters as required:
NOTE
Depending on the alarm type, some parameters are not available.
NOTE
Alarm descriptions are not configurable.
Parameter
severity { severity }
admin-enable
failrelay-enable
led-enable
auto-clear
Type commit and press Enter to save the changes, or type revert and press Enter to abort.
4.
Section 5.8
Managing Users
RUGGEDCOM ROX II allows for up to three user profiles to be configured locally on the device. Each profile
corresponds to one of the following access levels:
• Guest
• Operator
• Admin
The access levels provide or restrict the user's ability to change settings and execute various commands.
Rights
View Settings
Clear Logs
Reset Alarms
Clear Statistics
Change Basic Settings
Change Advanced Settings
Managing Users
Synopsis:   { emergency, alert, critical, error, warning, notice, info, debug }
The severity level can be one of emergency, alert, critical, error, warning, notice, info,
and debug. This cannot be changed for some alarms.
This parameter is mandatory.
If disabled, the alarm is not reported in the active list and does not actuate LED/failrelay.
If enabled, this alarm will assert the failrelay.
If enabled, the main 'Alarm' LED light will be red when this alarm is asserted. If disabled,
the main 'Alarm' LED light is not affected by this alarm.
If enabled, the LED and failrelay will be cleared automatically when condition is met.
Guest
ü
ü
û
û
û
û
Description
User Type
Operator
ü
ü
ü
ü
ü
û
Chapter 5
System Administration
Admin
ü
ü
ü
ü
ü
ü
111