Siemens RUGGEDCOM RS900 Installation Manual
Siemens RUGGEDCOM RS900 Installation Manual

Siemens RUGGEDCOM RS900 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS900:

Advertisement

RUGGEDCOM RS900
Installation Guide
6/2014
RC1024-EN-02
Preface
Introduction
Installing the Device
Communication Ports
Technical Specifications
Dimension Drawings
Certification
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RUGGEDCOM RS900

  • Page 1 Preface Introduction Installing the Device RUGGEDCOM RS900 Communication Ports Technical Specifications Dimension Drawings Installation Guide Certification 6/2014 RC1024-EN-02...
  • Page 2: Security Information

    Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 3: Table Of Contents

    RUGGEDCOM RS900 Installation Guide Table of Contents Table of Contents Preface ........................ Alerts ..............................v Related Documents ..........................v Accessing Documentation ........................v Training .............................. vi Customer Support ..........................vi Chapter 1 Introduction ......................1.1 Feature Highlights ........................1 1.2 Ports, Controls and Indicator LEDs ....................2 Chapter 2 Installing the Device ....................
  • Page 4 RUGGEDCOM RS900 Table of Contents Installation Guide 4.6 Mechanical Specifications ......................19 Chapter 5 Dimension Drawings ..................Chapter 6 Certification ......................6.1 Agency Approvals ........................23 6.2 FCC Compliance ........................23 6.3 Industry Canada Compliance ...................... 24 6.4 EMI and Environmental Type Tests ..................... 24...
  • Page 5: Preface

    Installation Guide Preface Preface This guide describes the RUGGEDCOM RS900. It describes the major features of the device, installation, commissioning and important technical specifications. It is intended for use by network technical support personnel who are responsible for the installation, commissioning and maintenance of the device.
  • Page 6: Training

    Siemens sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, please contact Siemens Customer Support through any of the following methods: • Online Visit http://www.siemens.com/automation/support-request...
  • Page 7: Introduction

    Introduction Introduction The RUGGEDCOM RS900 is a nine-port industrially hardened, fully managed, Ethernet switch specifically designed to operate reliably in electrically harsh and climatically demanding environments. The RS900 provides a high level of immunity to electromagnetic interference and heavy electrical surges typical of environments found on plant floors or in curb side traffic control cabinets.
  • Page 8: Ports, Controls And Indicator Leds

    Chapter 1 RUGGEDCOM RS900 Introduction Installation Guide ▪ Exceeds IEC 61850-3 (electric utility substations) ▪ Exceeds IEC 61800-3 (variable speed drive systems) ▪ Exceeds IEC 61000-6-2 (generic industrial) ▪ Exceeds NEMA TS-2 (traffic control equipment) • Hazardous Location Certification: Class 1 Division 2 •...
  • Page 9 RUGGEDCOM RS900 Chapter 1 Installation Guide Introduction Power Indicator LEDs The power indicator LED illuminates when power is being supplied to the device. Alarm Indicator LED The alarm indicator LED illuminates when an alarm condition exists. Reset Button The reset button shuts down and restarts the device.
  • Page 10 RUGGEDCOM RS900 Chapter 1 Installation Guide Introduction Ports, Controls and Indicator LEDs...
  • Page 11: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens Canada Ltd. could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 12: Mounting The Device On A Din Rail

    Chapter 2 RUGGEDCOM RS900 Installing the Device Installation Guide The following sections describe the various methods of mounting the device: • Section 2.1.1, “Mounting the Device on a DIN Rail” • Section 2.1.2, “Mounting the Device to a Panel” Section 2.1.1...
  • Page 13: Connecting Power

    RUGGEDCOM RS900 Chapter 2 Installation Guide Installing the Device Place the device against the panel and align the adapters with the mounting holes. Figure 3: Panel Mounting 1. Screw 2. Panel Adaptor Install the supplied screws to secure the adapters to the panel.
  • Page 14: Connecting High Ac/Dc Power

    Chapter 2 RUGGEDCOM RS900 Installing the Device Installation Guide IMPORTANT! Use only #16 gage copper wiring when connecting terminal blocks. The following sections describe how to connect power to the device: • Section 2.2.1, “Connecting High AC/DC Power” • Section 2.2.2, “Connecting Low DC Power”...
  • Page 15: Connecting Low Dc Power

    RUGGEDCOM RS900 Chapter 2 Installation Guide Installing the Device Figure 4: Terminal Block Wiring 1. Positive/Live (+/L) Terminal 2. Negative/Neutral (-/N) Terminal 3. Surge Ground Terminal 4. Braided Ground Cable Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 16 Chapter 2 RUGGEDCOM RS900 Installing the Device Installation Guide Figure 5: Terminal Block Wiring - Single DC Power Supply Inputs 1. Positive Terminal 2. Negative Terminal 3. Surge Ground Terminal 4. Braided Ground Cable Figure 6: Terminal Block Wiring - Dual DC Power Supply Inputs 1.
  • Page 17: Connecting The Failsafe Alarm Relay

    RUGGEDCOM RS900 Chapter 2 Installation Guide Installing the Device Connect the negative wire from the power source to the negative terminal on the terminal block. Using a braided wire or other appropriate grounding wire, connect the surge ground terminal to the chassis ground connection.
  • Page 18: Cabling Recommendations

    Section 2.5 Cabling Recommendations Siemens does not recommend the use of copper cabling of any length for critical, real-time substation automation applications. All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against damage from electrical transients and conform with IEC 61850-3 and IEEE 1613 Class 1 standards.
  • Page 19: Communication Ports

    RUGGEDCOM RS900 Chapter 3 Installation Guide Communication Ports Communication Ports The RS900 can be equipped with various types of communication ports to enhance its abilities and performance. To determine which ports are equipped on the device, refer to the factory data file available through ROS. For more information on how to access the factory data file, refer to the ROS User Guide for the RS900.
  • Page 20: Fiber Optic Ethernet Ports

    Chapter 3 RUGGEDCOM RS900 Communication Ports Installation Guide WARNING! Electric shock hazard – risk of serious personal injury and/or equipment interference. If shielded cables are used, make sure the shielded cables do not form a ground loop via the shield wire and the RJ45 receptacles at either end.
  • Page 21 RUGGEDCOM RS900 Chapter 3 Installation Guide Communication Ports Figure 12: LC Port Figure 11: MTRJ Port 1. Tx Connector 2. Rx Connector 1. Tx Connector 2. Rx Connector Figure 13: SC Port Figure 14: ST Port 1. Tx Connector 2. Rx Connector 1.
  • Page 22 RUGGEDCOM RS900 Chapter 3 Installation Guide Communication Ports Fiber Optic Ethernet Ports...
  • Page 23: Technical Specifications

    RUGGEDCOM RS900 Chapter 4 Installation Guide Technical Specifications Technical Specifications The following sections provide important technical specifications related to the device and available modules: • Section 4.1, “Power Supply Specifications” • Section 4.2, “Failsafe Relay Specifications” • Section 4.3, “Copper Ethernet Port Specifications”...
  • Page 24: Copper Ethernet Port Specifications

    To convert from peak to average, subtract 3 dBm. • Maximum segment length is greatly dependent on factors such as fiber quality, and the number of patches and splices. Consult a Siemens sales associate when determining maximum segment distances. Power...
  • Page 25: Operating Environment

    RUGGEDCOM RS900 Chapter 4 Installation Guide Technical Specifications Power Connector Cable Tx min. Tx max. Distance Mode Tx λ (nm) Sensitivity Saturation Budget Type Type (μm) (dBm) (dBm) (km) (dBm) (dBm) (dB) 1310 9/125 1310 9/125 Typical. Section 4.5 Operating Environment...
  • Page 26 RUGGEDCOM RS900 Chapter 4 Installation Guide Technical Specifications Mechanical Specifications...
  • Page 27: Dimension Drawings

    RUGGEDCOM RS900 Chapter 5 Installation Guide Dimension Drawings Dimension Drawings NOTE All dimensions are in millimeters, unless otherwise stated. 65.126 116.586 2.540 Figure 15: Overall Dimensions...
  • Page 28 Chapter 5 RUGGEDCOM RS900 Dimension Drawings Installation Guide 13.639 101.600 11.176 78.740 120.650 Figure 16: Panel and DIN Rail Mount Dimensions...
  • Page 29: Certification

    RUGGEDCOM RS900 Chapter 6 Installation Guide Certification Certification The RS900 device has been thoroughly tested to guarantee its conformance with recognized standards and has received approval from recognized regulatory agencies. • Section 6.1, “Agency Approvals” • Section 6.2, “FCC Compliance”...
  • Page 30: Industry Canada Compliance

    Chapter 6 RUGGEDCOM RS900 Certification Installation Guide Section 6.3 Industry Canada Compliance CAN ICES-3 (A) / NMB-3 (A) Section 6.4 EMI and Environmental Type Tests The RS900 has passed the following EMI and environmental tests. IEC 61850-3 Type Tests Test...
  • Page 31 RUGGEDCOM RS900 Chapter 6 Installation Guide Certification Test Description Test Levels Severity Levels DC Power ports 2.5 kV common, 1 kV differential mode @ 1 MHz AC Power ports 2.5 kV common, 1 kV differential mode @ 1 MHz IEC 61000-4-16...
  • Page 32: Environmental Type Tests

    Chapter 6 RUGGEDCOM RS900 Certification Installation Guide IEEE 1613 IEEE Test Description Test Levels Clause AC Power ports 2 kVAC Environmental Type Tests Test Description Test Levels Severity Levels IEC 60068-2-1 Cold Temperature Test Ad -40 °C (-40 °F), 16 Hours...

Table of Contents