Communication Mode
Set the communication mode of the own station. Select the communication mode from "Normal" or "High-Speed".
Item
Communication Mode
• In "High-Speed" mode, the maximum number of points assigned to RWw/RWr is 256 points per local
station.
• In "High-Speed" mode, the priority of transient transmission is lower and its processing speed is slower than
in "Normal" mode.
Parameter Name
Set a name for the module parameter if desired.
Item
Parameter Name
Dynamic Routing
Select whether to enable the dynamic routing function.
Item
Dynamic Routing
For details, refer to the following.
Page 37 Communications with different networks
Event Reception from Other Stations
Select whether to obtain the events occurring in the other stations.
Item
Event Reception from Other Stations
2 PARAMETER SETTINGS
76
2.4 Application Settings
Description
Normal
• Cyclic and transient transmission are performed without losing their
inherent speed performance. This mode is suitable for a system that
transmits large amount of data for management, monitoring, and
diagnostics by transient transmission along with I/O control or analog
control. (Page 177 Differences in Cyclic Transmission Modes)
High-Speed
• Cyclic transmission has a priority over transient transmission. This mode is
suitable for applications requiring lower cycle times such as I/O control,
analog control, and digital I/O. (Page 177 Differences in Cyclic
Transmission Modes)
Description
Set a name for the module parameter if desired.
Description
When communicating with different networks, select whether to enable the
dynamic routing function.
Description
Select whether to obtain the events occurring in the other stations.
Setting range
• Normal
• High-Speed
(Default: High-Speed)
Setting range
Up to 8 one-byte or two-byte
characters
(Default: Blank)
Setting range
• Enable
• Disable
(Default: Enable)
Setting range
• Enable
• Disable
(Default: Enable)