■Performing interlink transmission in a multiple CPU system
When different control CPUs are set for the network modules, interlink transmission cannot be performed using interlink
transmission parameters or a program. Perform interlink transmission using data communication by the CPU buffer memory.
(MELSEC iQ-R CPU Module User's Manual (Application))
Setting example
The following is a setting example to perform interlink transmission from the master station on CC-Link IE Field Network to
stations on CC-Link IE Controller Network. In this example, 128-point data input from the slave station (station No.1) is
transferred.
Slave station
(station No.1)
128
Input
points
CC-Link IE
Field Network
1.
Select "0000: RD77GF16 (Master Station)" for "Transfer Source Module" and "0020: RJ71GP21-SX (Normal Station)" for
"Transfer Destination Module", and enter the transfer ranges of link devices.
2.
Click the [OK] button.
2 PARAMETER SETTINGS
80
2.4 Application Settings
Master station
(station No.0)
Normal station
(Simple Motion module)
(station No.4)
RX
LB
RX200
RX27F
LB780
LB7FF
CC-Link IE
Controller Network
Normal station
(station No.3)
Station No.1 send
range
Station No.2 send
range
Station No.3 send
range
Station No.4 send
range
Control station
(station No.1)
Normal station
(station No.2)