Mitsubishi Electric RD77GF8 User Manual page 74

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

Item
1 to 256
Link Side
CPU Side
The link devices of the Simple Motion module can be accessed from a program. (Page 23 Direct access
to link devices)
2 PARAMETER SETTINGS
72
2.3 Basic Settings
Description
Set the link refresh ranges of RX, RY, RWr, and RWw. Up to 256 ranges can be
set. (Page 21 Link refresh)
Ex.
0000H
Device
name
(RX)
00FFH
0000H
Device
name
(RY)
00FFH
0000H
Device
name
(RWr)
00FFH
0000H
Device
name
(RWw)
00FFH
Simple Motion module
Transfer
1000H
1
Device
name
(X)
10FFH
Transfer
1000H
2
Device
name
(Y)
10FFH
Transfer
000000H
3
Device
name
(W)
0000FFH
Transfer
001000H
4
Device
name
(W)
0010FFH
CPU module
Setting range
Device Name
• RX, RY, RWr, RWw
(Default: Blank)
Points
• RX, RY: 16 to 16384
• RWr, RWw: 4 to 8192
(Default: Blank)
Start
• RX, RY: 0H to 3FF0H (set in increments of
16 points)
• RWr, RWw: 0 to 1FFCH (set in increments
of 4 points)
(Default: Blank)
End
• RX, RY: 0H to 3FFFH (set in increments of
16 points)
• RWr, RWw: 0 to 1FFFH (set in increments
of 4 points)
(Default: Blank)
Target
• Specify Device
(Default: Blank)
Device Name
• Specify Device (when link side is RX): X, M,
L, B, D, W, R, ZR, RD
• Specify Device (when link side is RY): Y, M,
L, B, D, W, R, ZR, RD
• Specify Device (when link side is RWr): M,
L, B, D, W, R, ZR, RD
• Specify Device (when link side is RWw): M,
L, B, D, W, R, ZR, RD
(Default: Blank)
Points, Start, End
• Range of the device in the CPU module
• Set bit devices in increments of 16 points
and word devices in increments of 4 points.
(Default: Blank)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd77gf4Rd77gf16Rd77gf32

Table of Contents