Mitsubishi Electric RD77GF8 User Manual page 166

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

No.
Name
SW0198
Link dedicated
instructions processing
result CH3
SW0199
Link dedicated
instructions processing
result CH4
SW019A
Link dedicated
instructions processing
result CH5
SW019B
Link dedicated
instructions processing
result CH6
SW019C
Link dedicated
instructions processing
result CH7
SW019D
Link dedicated
instructions processing
result CH8
SW01C0
Information of CC-Link
to
IE Field Network
SW01C7
synchronous
communication function
of each station
SW01C8
Synchronous/
to
asynchronous operating
SW01CF
status information of
each station
APPX
164
Appendix 4 List of Link Special Register (SW)
Description
Stores the processing results of the link dedicated instruction that used channel 3 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 4 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 5 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 6 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 7 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the processing results of the link dedicated instruction that used channel 8 of the own station.
0: Completed normally
1 or greater: Completed with an error (Error code is stored.)
Stores the information about support or non-support of CC-Link IE Field Network synchronous communication function
for each station.
0: Not supported
1: Supported
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW01C0
16 15 14 13 12 11 10
SW01C1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW01C2
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW01C3
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW01C4
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW01C5
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW01C6
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW01C7
Each No. in the table represents a station No.
 is fixed to 0.
(Conditions)
• This register is enabled when "Baton pass status of own station" (SB0047) is off.
• When "Baton pass status of own station" (SB0047) is turned on (error), data prior to error is held.
• This register is enabled only for normally operating stations in "Baton pass status of each station" (SW00A0 to
SW00A7).
• Stations higher than the maximum station No. are ignored.
Stores the information about operating status of CC-Link IE Field Network synchronous communication function for
each station.
0: Asynchronous setting
1: Synchronous setting
Stations which are not executing an inter-module synchronous interrupt program because the CPU operating status is
currently a status such as STOP, that is unable to execute the program, are also treated as an asynchronous setting.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
SW01C8
16 15 14 13 12 11 10
SW01C9
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
SW01CA
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
SW01CB
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
SW01CC
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
SW01CD
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
SW01CE
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
SW01CF
Each No. in the table represents a station No.
 is fixed to 0.
(Conditions)
• This register is enabled when "Baton pass status of own station" (SB0047) is off.
• When "Baton pass status of own station" (SB0047) is turned on (error), data prior to error is held.
• This register is enabled only for normally operating stations in "Baton pass status of each station" (SW00A0 to
SW00A7).
• Stations higher than the maximum station No. are ignored.
9
8
7
6
5
4
3
2
120 119 118 117 116 115 114 113
9
8
7
6
5
4
3
2
120 119 118 117 116 115 114 113
1
1

Hide quick links: