Mitsubishi Electric RD77GF8 User Manual page 126

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

Remote Operation
This function executes remote operations (such as RUN, STOP, and RESET operations) to the station selected on the "CC-
Link IE Field Diagnostics" window, from the engineering tool.
The displayed window varies depending on the station selected. For the operations with a module other than a Simple Motion
module selected, refer to the manual for the module used.
■Procedure
To perform remote operations, follow the steps below.
*1 To perform remote RESET, preset "Remote Reset Setting" under "Operation Related Setting" of "CPU Parameter" to "Enable".
For details on the remote operations, refer to user's manual for the CPU module used.
4 TROUBLESHOOTING
124
4.3 Checking the Network Status
1.
Select the module where the remote operations are
performed in the CC-Link IE Field Network diagnostics.
2.
Click the [Remote Operation] button in the "CC-Link IE Field
Diagnostics" window. Or right-click a module icon in the
"Network Status" and click [Remote Operation].
"Remote Operation" window is displayed.
3.
Specify the target station in "Specify Execution Target".
• "Currently Specified Station": The remote operations are
performed only to the CPU module on the station selected in
the CC-Link IE Field Network diagnostics.
• "Specify Group No.": When the target station is on CC-Link IE
Field Network, remote operations cannot be performed by
selecting this item. If performed, an error will occur.
• "All Stations Specified": The remote operations are performed
on all stations on the network selected under "Specify
Execution Target".
4.
Select a remote operation (RUN, STOP, PAUSE, or
RESET) to be performed in "Operation".
5.
Click the [Execute] button to perform the remote operation.
*1