 Use the same Nos. for the first and second octets of the IP addresses of the request source device, request destination device, and modules between them.
192 . 168 . 10 . 36
The first and second octets (network addresses)
 For the IP addresses of the Ethernet-equipped modules, set a No. between 1 and 239 for the third octet and a No. between 1 and 120 for the fourth octet.
The network No. of the own station is automatically assigned to the third octet of the IP address of the Simple Motion module and remote head modules
each. The station No. of the own station is automatically assigned to the fourth octet of the IP address of the Simple Motion module or remote head modules
each. (The fourth octet of the IP address of the master station is always 125.)
The third octet
192 . 168 . 10 . 36
The fourth octet
 Use the same No. for the third octet (network No.) of the IP addresses of an Ethernet device and a Ethernet-equipped module connected to the Ethernet
device.
Ethernet device
(request source device)
192.168.10.11
Network No.10
 Do not use the third octet (network No.) of the IP address same as that of other network modules and other CPU modules using the IP packet transfer
function.
Do not use the same network Nos. for those highlighted.
192.168.10.1
Network No.10
Ethernet
*2 Do not use the same network Nos. for those of network modules other than the Simple Motion module.
 The values in the first and second octets of the remote head module IP address are obtained from the master station IP address so that the same values as
those of the master station can be set.
1 FUNCTIONS
44
1.5 IP Packet Transfer Function
IP address setting
not required
192.168.2.125
Ethernet-
Master
equipped
station
module
Station
No.0
192.168.10.36
Network No.2
192.168.10.2
Simple Motion module
192.168.7.18
Ethernet-
Local
Local
equipped
station
station
module
Station
Station
No.8
No.18
192.168. 2.8
Network No.1
Network No.2
CC-Link IE Field Network
Network No.32
*2
Ethernet
192.168.21.2
192.168.21.1
Network No.21
Ethernet