Mitsubishi Electric RD77GF8 User Manual page 70

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

Item
RX/RY Setting
RWw/RWr Setting
Reserved/Error Invalid
Station/System
Switching Monitoring
Target Station
Pairing
Network Synchronous
Communication
Alias
Comment
Station-specific mode
setting
Module List
■Parameter processing of a slave station
Select the module in the list of stations.  [CC IE Field Configuration]  [Online]  [Parameter Processing of Slave
Station]
The parameters of a slave station can be set or read. This setting can be executed only when the slave station supports the
parameter processing. The setting range varies depending on the target module. For details, refer to the manual for the slave
station used.
■Command execution of a slave station
Select the module in the list of stations.  [CC IE Field Configuration]  [Online]  [Command Execution of Slave
Station]
The command of a slave station is executed. This setting can be executed only when the slave station supports the command
execution. The setting range varies depending on the target module. For details, refer to the manual for the slave station
used.
2 PARAMETER SETTINGS
68
2.3 Basic Settings
Description
Assign RX/RY points. (Page 18 Data flow and link device assignment)
Points can be assigned in increments of 16 (Start: _ _ _0H, End: _ _ _FH).
To equally assign points or the same points, go to [Equal Assignment] or [Identical Point
Assignment] on the [CC IE Field Configuration] menu.
Assign RWw/RWr points in increments of 4. (Page 18 Data flow and link device
assignment)
To equally assign points or the same points, go to [Equal Assignment] or [Identical Point
Assignment] on the [CC IE Field Configuration] menu.
Set this item to set the slave station as a reserved station, error invalid station, or system
switching monitoring target station.
• No Setting: The slave station is connected to the network.
• Reserved Station: The slave station is reserved for future expansion. By reserving a
slave station, link device assignment will not change even if the slave station is added or
the reservation is canceled. Therefore, the program needs not to be modified. Physical
connection of the slave station is not required.
• Error Invalid Station: Even if a slave station is disconnected during data link, the master
station will not detect the slave station as a faulty station.
• System Switching Monitoring Target Station: This item cannot be set in the Simple
Motion module.
This item cannot be set in the Simple Motion module.
Select whether to synchronize the slave station using the CC-Link IE Field Network
synchronous communication function.
This item cannot be set in the Simple Motion module.
Set the station-specific mode of the slave station. This setting is available only when the
slave station supports the station-specific mode.
The slave stations are listed. Drag the modules from "Module List" to the list of stations or
the network map to set the information of the slave stations into the master station.
Setting range
Points
• Master Station, Local Station,
Intelligent Device Station: 16 to 2048
• Remote Device Station: 16 to 128
• Remote I/O Station: 16 to 64
Device No.
• 0H to 3FFFH
(Default: Varies depending on the set
module)
Points
• Master Station, Local Station,
Intelligent Device Station: 4 to 1024
• Remote Device Station: 4 to 64
• Remote I/O Station: Cannot be set.
Device No.
• 0H to 1FFFH
(Default: Varies depending on the set
module)
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
• Asynchronous
• Synchronous
(Default: Asynchronous)
All settings are invalid.
The setting varies depending on the
set module.