Mitsubishi Electric RD77GF8 User Manual page 60

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

■Setting in the Ethernet adapter module 2 (station No.1)
Use the configuration tool to set the IP address.
1.
Set the IP address in the Ethernet adapter module 2 (Ethernet part) as follows.
Setting item tree  NZ2GF-ETB  [Parameter]  "Ethernet"
2.
The IP address setting is not required for the Ethernet adapter module 2 (CC-Link IE Field Network part).
The network address set in the master station 2 (station No.0) is automatically assigned.
3.
The CC-Link IE Field Network gateway setting is not required for the Ethernet adapter module 2.
Because the network address of the request destination (Ethernet adapter module 1) is the same as that of the master station,
setting only the communication path in the routing parameters allows communications to be performed with the request
destination.
4.
Write the set parameters to the Ethernet adapter module 2.
1 FUNCTIONS
58
1.5 IP Packet Transfer Function