Event List

This section lists the events which occur in CC-Link IE Field Network.
System and operation are included in the event types.
System
Event code
Overview
00100
Link-up
00130
Receive frame error
00500
<<Own station>> Baton pass return (network entry)
00501
<<Another station>> Baton pass return (network
entry)
00502
All stations baton pass normalization (network entry
in all stations)
00510
<<Own station>> Data link restart (cyclic
transmission started)
00511
<<Another station>> Data link restart (cyclic
transmission started)
00512
All stations data link normalization (cyclic
transmission in all stations started)
00513
<<Own station>> Data link start instruction
acceptance
00514
<<Own station>> Data link stop instruction
acceptance
00520
<<Own station>> Temporary error invalid station
setting instruction acceptance
00521
<<Own station>> Temporary error invalid station
cancel instruction acceptance
00524
<<Another station>> Temporary error invalid station
setting execution
00525
<<Another station>> Temporary error invalid station
cancel execution
00530
<<Own station>> Reserved station cancel setting
instruction acceptance
00531
<<Own station>> Reserved station enable setting
instruction acceptance
00534
<<Another station>> Reserved station cancel
setting execution
00535
<<Another station>> Reserved station enable
setting instruction execution
00541
Receive parameter error resolution
00542
<<Own station>> Receive frame error line status
caution level
00543
<<Another station>> Receive frame error line status
caution level
00800
Link-down
00C00
<<Own station>> Baton pass interruption
(departure from network)
00C01
<<Another station>> Baton pass interruption
(departure from network)
00C02
Response error from/to another station
00C10
<<Own station>> Data link stop (cyclic transmission
stopped)
Cause
Link-up has occurred when the network cable connected to the external device was
connected.
Receive frame error was detected. Or, the network whose network type is different was
connected.
Baton pass of the own station was returned from interruption status to normal status.
Baton pass of another station was returned from interruption status to normal status.
Baton pass was returned to normal status at all stations.
Data link of the own station was restarted.
Data link of another station was restarted.
Data link was returned to normal status at all stations.
Data link startup of the own station instruction was received.
Data link stop instruction of the own station was received.
Temporary error invalid station setting instruction was received.
Temporary error invalid station cancel instruction was received.
Temporary error invalid station was set at another station.
Temporary error invalid station was canceled at another station.
Reserved station cancel setting instruction was received.
Reserved station enable setting instruction was received.
Reserved station cancel setting was executed at another station.
Reserved station enable setting was executed at another station.
A parameter error received from master station/control station was resolved. (Normal
parameter was received.)
A receive frame error (line status: caution level) has been occurred.
A receive frame error (line status: caution level) has been occurred.
Link-down occurred when network cable connected to the external device was
disconnected.
Baton pass of the own station was interrupted.
Baton pass of another station was interrupted.
• Abnormal response was returned from another station when accessing another
station.
• Abnormal response was returned to another station when accessed from another
station.
Data link of the own station was stopped.