■Selecting the target module in the "Reserved Station Function Enable" window
Reservation of multiple slave stations can be temporarily canceled through the "Reserved Station Function Enable" window all
at once.
To temporarily cancel a reservation, follow the steps below.
To reserve the slave station again, follow the steps below.
4 TROUBLESHOOTING
120
4.3 Checking the Network Status
1.
Connect a slave station specified as a
reserved station to the network.
2.
Click the [Reserved Station Function Enable]
button in the "CC-Link IE Field Diagnostics"
window.
"Reserved Station Function Enable" window is
displayed.
3.
In "Reserved Station List", click the No. of the
target station. The text turns red and the
background turns orange.
Only reserved stations can be selected. The
background of a reserved station No. is displayed
in light blue.
4.
Click the [OK] button to temporarily cancel the
reservation.
5.
Debug the slave station that has been added.
1.
Open the "Reserved Station Function Enable"
window in the same way as described in the
procedure for temporarily canceling a
reservation.
2.
In "Reserved Station List", click the No. of the
target station. The text turns red and the
background turns light blue.
Only stations not specified as a reserved station
can be selected.
The background of available modules is orange.
3.
Click the [OK] button to set the station as a
reserved station again.