Mitsubishi Electric RD77GF8 User Manual page 124

Melsec iq-r series, simple motion module
Table of Contents

Advertisement

■Selecting the target module in the "Enable/Disable Ignore Station Errors" window
Temporary error invalid station setting can be configured to multiple slave stations through the "Enable/Disable Ignore Station
Errors" window all at once.
To set a temporary error invalid station, follow the steps below.
To cancel temporary error invalid station setting, follow the steps below.
4 TROUBLESHOOTING
122
4.3 Checking the Network Status
1.
Click the [Enable/Disable Ignore Station
Errors] button in the "CC-Link IE Field
Diagnostics" window.
"Enable/Disable Ignore Station Errors" window is
displayed.
2.
In "Ignore Station Error List", click the No. of
the target station. The text turns red and the
background turns yellow.
Only stations for which temporary error invalid
station setting has not been configured can be
selected. The background of available modules is
white.
3.
Click the [OK] button to temporarily set the
station as an error invalid station.
1.
Open the "Enable/Disable Ignore Station
Errors" window in the same way as described
in the procedure for setting a temporary error
invalid station.
2.
In "Ignore Station Error List", click the No. of
the target station. The text turns red and the
background turns white.
Only temporary error invalid stations can be
selected. The background of a temporary error
invalid station No. is displayed in yellow.
3.
Click the [OK] button to cancel temporary error
invalid station setting.