Door switches and lights
Label in English
1
READY
2
RUN
3
FAULT
4
MAIN CONT.
OFF ON
5
EMERGENCY
STOP RESET
6
EMERGENCY
STOP
Main switch-disconnector Q1
The switch-disconnector handle switches the main voltage to the drive on and off.
■
Control panel
The ACS-AP-S is the user interface of the drive. It provides the essential controls such as
Start/Stop/Direction/Reset/Reference, and the parameter settings for the control program.
One control panel can be used to control several drives through a panel link.
The control panel can be removed by pulling it forward from the top edge and disconnecting
the panel cable. The panel is reinstalled in reverse order. For the use of the control panel,
1
4
6
Label in local
Description
language
-
Ready pilot light (option +G327)
-
Run pilot light (option+G328)
-
Fault pilot light (option +G329)
-
Operating switch with option +F250
0 Opens the main contactor (Q2) and disables starting of the drive
1 Closes the main contactor (Q2)
-
Emergency stop indication light and reset push button with options
+Q951 and +Q963
-
Emergency stop push button with options +Q951 and +Q963
Operation principle and hardware description 37
2
3
5