Us - With Option +E205 - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

Frame
size
Max. wire
size
AWG
R6
3×300
MCM
R7
3×500
MCM
R8
2×(3×300
MCM)
R9
2×(3×500
MCM)
R10
4×(3×300
MCM)
R11
4×(3×500
MCM)
1)
Note: Minimum wire size does not necessarily have enough current capability for full load.
Make sure the installation complies with local laws and regulations.
2)
-01-246A-4: 2×1/0, -01-293A-4: 2×3/0
US – With option +E205
Input and motor cable terminal bolt sizes, maximum accepted wire sizes (per three phases)
and tightening torques are given below.
Frame size
Max. wire size
R6
3×300 MCM
R7
3×500 MCM
R8
2×(3×300 MCM)
R9
2×(3×500 MCM)
R10
4×(3×300 MCM)
R11
4×(3×500 MCM)
L1, L2, L3
Bolt size
Tighten-
ing torque
lbf·ft
M10 (3/8")
22.1
M10 (3/8")
22.1
M10 (3/8")
22.1
M12
51.6
(7/16")
M12
51.6
(7/16")
M12
51.6
(7/16")
L1, L2, L3, U2, V2, W2
Bolt size
2
mm
M10 (3/8")
M10 (3/8")
M12 (7/16")
M12 (7/16")
M12 (7/16")
M12 (7/16")
T1/U2, T2/V2, T3/W2
Min. wire
Max. wire
1)
size
size
ing torque
AWG
AWG
3
3×300
MCM
3/0
3×500
MCM
2×1/0 /
2×(3×300
2)
2×3/0
MCM)
2×3/0
2×(3×500
MCM)
-
4×(3×300
MCM)
-
4×(3×500
MCM)
Tightening
torque
N·m
22.1
22.1
51.6
51.6
51.6
51.6
Technical data 161
PE (grounding)
Tighten-
Bolt size
ing torque
lbf·ft
22.1
M10 (3/8")
22.1
M10 (3/8")
22.1
M10 (3/8")
51.6
M10 (3/8")
51.6
M10 (3/8")
51.6
M10 (3/8")
PE (grounding)
Bolt size
Tightening
torque
2
mm
N·m
M10
30...44
M10
30...44
M10
30...44
M10
30...44
M10
30...44
M10
30...44
Tighten-
lbf·ft
29.5
29.5
29.5
29.5
29.5
29.5

Advertisement

Table of Contents
loading

Table of Contents