General Cabling Instructions; Wiring - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

Transistor output
Marking
42
DO1 SRC
43
DO1 OUT
44
DO1 SGND
External power supply
The external power supply is needed only if you want to connect an external back-up power
supply for the drive control unit.
Note:
Frames R1...R5 need CMOD-01 for connecting external power supply, frames R6...R9
have corresponding terminals 40 and 41 on the control unit.
Marking
40
24V AC/DC + in
41
24V AC/DC - in

General cabling instructions

Obey the instructions given in chapter Planning the electrical installation.

Wiring

Connect the external control cables to the applicable module terminals. Ground the outer
shield of the cables 360 degrees under a grounding clamp on the grounding shelf of the
control cables.
Relay output connection example
24 V DC
Digital output connection example
24 V DC
Frequency output connection example
Description
Source input
Digital or frequency output
Ground (earth) potential
Description
External 24 V (AC/DC) input
External 24 V (AC/DC) input
RO4C
50
RO4A
51
RO4B
52
42
DO1 SRC
DO1 OUT
43
DO1 SGND
44
Optional I/O extension modules 243
CMOD-01
CMOD-01