Technical Data - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

102 Control unit
Remove the jumpers before connecting an external Safe torque off circuitry to the drive.
See also chapter
Safe torque off function (page
Note:
Only 24 V DC can be used for STO. Only PNP input configuration can be used.

Technical data

External power supply
Term. 40, 41
+24 V DC output
(Term. 10)
Digital inputs DI1...DI6
(Term. 13...18)
Relay outputs RO1...RO3
(Term. 19...27)
Analog inputs AI1 and AI2
(Term. 2 and 5)
Maximum power: 36 W, 1.50 A at 24 V AC/DC ±10% as standard
Terminal size: 0.14...2.5 mm
Total load capacity of this outputs is 6.0 W (250 mA / 24 V) minus the power
taken by the option modules installed on board.
Terminal size: 0.14...2.5 mm
Input type: NPN/PNP
Terminal size: 0.14...2.5 mm2
DI1...DI5 (Term.13...17)
12/24 V DC logic levels: "0" < 4 V, "1" > 8 V
R
: 3 kohm
in
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
DI5 (Term.17)
Can be used as a digital or frequency input.
12/24 V DC logic levels: "0" < 3 V, "1" > 8 V
R
: 3 kohm
in
Max. frequency 16 kHz
Symmetrical signal (duty cycle D = 0.50)
DI6 (Term.18)
Can be used as a digital or frequency input.
12/24 V DC logic levels: "0" < 3 V, "1" > 8 V
R
: 3 kohm
in
Max. frequency 16 kHz
Symmetrical signal (duty cycle D = 0.50)
Hardware filtering: 0.04 ms, digital filtering: 2 ms sampling
Note:
DI6 is not supported in the NPN configuration.
PTC mode – PTC thermistor can be connected between DI6 and +24VDC:
< 1.5 kohm = '1' (low temperature), > 4 kohm = '0' (high temperature), open
circuit = '0' (high temperature).
DI6 is not a reinforced/double insulated input. Connecting the motor PTC
sensor to this input requires usage of a reinforced/double insulated PTC
sensor inside the motor
250 V AC / 30 V DC, 2 A Terminal size: 0.14...2.5 mm2
See section
Isolation areas (page
Current/voltage input mode selected with a dip switch, see
Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1) (page
Current input: 0(4)...20 mA, R
Voltage input: 0(2)...10 V, R
Terminal size: 0.14...2.5 mm
Inaccuracy: typical ±1%, max. ±1.5% of full scale
Inaccuracy for Pt100 sensors: 10 °C (50 °F)
221).
2
2
103).
: 100 ohm
in
: > 200 kohm
in
2
AI1 and AI2 as
101).