188 Technical data
Terminal and connection data for auxiliary control circuits
Maximum acceptable voltage and current values and wire sizes in terminal blocks are given
below.
Terminal block
X250
X289
X290
X300
X951
X969
X3
X504
X601.1
X601.1
Maximum acceptable voltage and current values and wire sizes
230V AC / 24V DC, 2A
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
230V AC / 24V DC, 2A
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
230V AC / 24V DC, 2A
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
230V AC, 4A
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
24V DC
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
24V DC
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
24V DC
• Solid wire 0,14...4 mm2 (28...12 AWG)
• Stranded wire 0,08...2,5 mm2 (28...14 AWG)
230V AC / 24V DC, 2A
• Solid wire 0,25...2,5mm2 (24...12 AWG)
• Stranded wire 0,25...2,5 mm2 (24...14 AWG)
480V AC, 20A
• Solid wire 0,75...16 mm2 (18...6 AWG)
• Stranded wire 0,75...16 mm2 (18...6 AWG)
230V AC / 24V DC, 2A
• Solid wire 0,2...2,5 mm2 (24...14 AWG)
• Stranded wire 0,2...2,5 mm2 (24...14 AWG)