Maximum Allowed Plinth Height For The Extraction/Installation Ramp; Typical Power Cable Sizes - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

158 Technical data
Maximum allowed plinth height for the
extraction/installation ramp
The maximum plinth height for the extraction/installation ramp delivered with the drive is 50
mm (1.97 in).

Typical power cable sizes

The table below gives typical copper and aluminum cable types with concentric copper
shield for the drives with nominal current. For the cable sizes accepted by the drive cabinet
cable entries and connection terminals, see
cables (page
160).
Drive type ACS580-07-
U
= 400 V
N
0145A-4
0169A-4
0206A-4
0246A-4
0293A-4
0363A-4
0430A-4
0505A-4
0585A-4
0650A-4
0725A-4
0820A-4
0880A-4
U
= 480 V
N
0124A-4
0156A-4
0180A-4
Frame
size
Cu cable type
2
mm
R6
3×95
R7
3×120
R7
3×150
R8
2×(3×70)
R8
2×(3×95)
R9
2×(3×120)
R9
2×(3×150)
R10
3x(3x95)
R10
3x(3x120)
R10
3x(3x150)
R11
3x(3x185)
R11
3x(3x240)
R11
3x(3x240)
R6
3x95
R7
3x120
R7
3x150
R6, R7: 400 mm (15.75") in)
R8, R9: 500 mm (19.68 in)
R10. R11: 800 mm (31.50 in)
Terminal and entry data for the power
1)
IEC
Al cable type
2
mm
3×120
3×150
3×240
2×(3×95)
2×(3×120)
2×(3×185)
2×(3×240)
3x(3x150)
4×(3x150)
4×(3x150)
4x(3x185)
4x(3x240)
4x(3x240)
3x120
3x150
3x240
2)
US
Cu cable type
AWG/kcmil per phase
3/0
250 MCM
300 MCM
2×2/0
2×3/0
2×250 MCM
2×300 MCM
2×500 MCM or 3×250
MCM
3x300 MCM
3x300 MCM
3×500 MCM or 4×300
MCM
3×600 MCM or 4×400
MCM
3×600 MCM or 4×400
MCM
3/0
250 MCM
300 MCM