154 Technical data
Changing the value of parameter 97.01 Switching frequency reference does not require
derating.

Fuses (IEC)

The standard drive is equipped with aR fuses listed below.
Drive type
Input cur-
ACS580-07-
rent
(A)
U
= 400 V
N
0145A-4
145
0169A-4
169
0206A-4
206
0246A-4
246
0293A-4
293
0363A-4
363
0430A-4
430
0505A-4
505
0585A-4
585
0650A-4
650
0725A-4
725
0820A-4
820
0880A-4
880
Note 1: See also
Implementing the emergency stop function (page
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Fuses with lower current rating can be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.

Fuses (UL)

The drive with option +C129 and option +F289 is equipped with standard fuses listed below
for internal circuit protection. The fuses restrict drive damage and prevent damage to adjoining
equipment in case of a short-circuit inside the drive. The drive also requires external fuses
for branch circuit protection per NEC, see section
protection (page
156).
Ultrarapid (aR) fuses (one fuse per phase)
2
(A)
A
s
250
31000
250
31000
315
52000
400
79000
500
155000
630
210000
700
300000
800
465000
900
670000
1000
945000
1250
1950000
1250
1950000
1400
2450000
V
Type
(Buss-
mann)
690
170M3816D
J320375C
690
170M3816D
J320375C
690
170M3817D
N320379C
690
170M5408
H300065A
690
170M5410
S1046930K
690
170M6410
X300078C
690
170M6411
Y300079C
690
170M6412
W1046956F
690
170M6413
X1046957F
690
170M6414
Y1046958F
690
170M6416
A1046960F
690
170M6416
A1046960F
690
170M6417
B1046961F
67).