Analog outputs AO1 and AO2
(Term. 7 and 8)
Reference voltage output for
analog inputs +10V DC (Term.
4)
Safe torque off (STO) inputs
IN1 and IN2 (Term. 37 and 38)
Control panel - drive
connection
Control panel - PC
connection
Isolation areas
Current/voltage output mode for AO1 selected with a dip switch, see
tion for obtaining 0...10 V from analog output 2 (AO2) (page
Current output: 0...20 mA, R
Voltage input: 0...10 V, R
Terminal size: 0.14...2.5 mm
Inaccuracy: ±1% of full scale (in voltage and current modes)
Max. 20 mA output Inaccuracy: ±1%
24 V DC logic levels: "0" < 5 V, "1" > 13 V
R
: 2.47 kohm
in
Terminal size: 0.14...2.5 mm
EIA-485, male RJ-45 connector, max. cable length 100 m
USB Type Mini-B, max. cable length 2 m
1...3
AI1
4...6
AI2
7...8
AO
10...12
24 V
GND
13...15
DI
16...18
DI
34...38
STO
SLOT 2
I/O extension
module
Panel port
Reinforced insulation (IEC/EN 61800-5-1:2007)
Functional insulation (IEC/EN 61800-5-1:2007)
: < 500 ohm
load
: > 100 kohm (AO1 only)
load
2
2
SLOT 1
Fieldbus module
Power unit
connection
EFB
EIA/R5-485
connection
40, 41
Ext. 24 V
19...21
RO1
22...24
RO2
25...27
RO3
Control unit 103
Connec-
99).