Alternative 2 - Using The Holes Inside The Cabinet; Miscellaneous; Cable Duct In The Floor Below The Cabinet; Arc Welding - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

Alternative 2 – Using the holes inside the cabinet

Miscellaneous

Cable duct in the floor below the cabinet

A cable duct can be constructed below the 500 mm wide middle part of the cabinet. The
cabinet weight lies on the two 50 mm wide transverse sections which the floor must carry.
Prevent the cooling air flow from the cable duct to the cabinet by bottom plates. To ensure
the degree of protection for the cabinet, use the original bottom plates delivered with the
unit. With user-defined cable entries, take care of the degree of protection, fire protection
and EMC compliance.

Arc welding

ABB does not recommend attaching the cabinet by arc welding. However, if arc welding is
the only option, connect the return conductor of the welding equipment to the cabinet frame
at the bottom within 0.5 meters (1'6") of the welding point.
Note:
The thickness of the zinc plating of the cabinet frame is 100 to 200 micrometers (4 to 8 mil).
WARNING!
Make sure that the return wire is connected correctly. Welding current must not
return via any component or cabling of the drive. If the welding return wire is
1. Attach the cabinet to the floor through the bottom
2. If the back attaching holes are not accessible, at-
50 (1.97")
500 (19.68")
Mechanical installation 53
attaching holes with M10 to M12 (3/8" to 1/2") bolts.
The recommended maximum distance between
the front edge attaching points is 800 mm (31.5").
tach the cabinet at the top to wall with L-brackets
(not included in the delivery) using the lifting lug
attaching holes.
M16
50 (1.97")

Advertisement

Table of Contents
loading

Table of Contents