N

Selecting the power cables

General rules

Select the input power and motor cables according to local regulations:
Select a cable capable of carrying the drive nominal current. See section
Ratings (page 149)
Select a cable rated for at least 70 °C maximum permissible temperature of conductor
in continuous use.
Make sure that the inductance and impedance of the PE conductor/cable (grounding
wire) are rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault occurs).
600 V AC cable is accepted for up to 500 V AC.