Connecting External Wiring To The Control Unit Or Optional I/O Terminal Block - ABB ACS580-07 Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580-07:
Table of Contents

Advertisement

88 Electrical installation
The route of the control cables for frames R10 and R11 is shown below.
X504 (+L504)
Connecting external wiring to the control unit or optional I/O terminal
block
Note:
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting the wire
with its return wire reduces disturbances caused by inductive coupling.
Note:
Leave slack to the control wires to make it possible to lift the control unit mounting plate a
little when the drive module is replaced.
Ground the pair-cable shields and all grounding wires to the grounding clamp.

Advertisement

Table of Contents
loading

Table of Contents