156 Technical data
Drive type
Input current
ACS580-07-
U
= 480 V
N
0145A-4
0169A-4
0206A-4
0246A-4
0293A-4
0363A-4
0430A-4
Note 1: See also
Implementing the emergency stop function (page
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Fuses with lower current rating can be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
Note 4: Circuit breakers must not be used without fuses.

Fuses for branch circuit protection

The drive is suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes at 480 V maximum when the input cable is protected with UL class
T or L fuses. The fuses for branch circuit protection per NEC must be selected according
to the table below. Fast acting class T and L or faster are recommended in the USA. Obey
local regulations.
Drive type
Input
current
ACS580-07-
A
U
= 460 V
N
0145A-4
124
0169A-4
156
0206A-4
180
0246A-4
240
0293A-4
260
0363A-4
361
0430A-4
414
0505A-4
483
0585A-4
573
0650A-4
623
Fuse (one fuse per phase) with option +F289
A
A
124
250
156
250
180
315
240
400
260
500
361
630
414
700
Fuse (one fuse per phase)
A
V
Manufacturer
200
600
225
600
300
600
350
600
400
600
500
600
600
600
600
600
800
600
800
600
Manufacturer
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Type
Bussmann
JJS-200
Bussmann
JJS-225
Bussmann
JJS-300
Bussmann
JJS-350
Bussmann
JJS-400
Bussmann
JJS-500
Bussmann
JJS-600
Bussmann
JJS-600
Ferraz
A4BY800
Ferraz
A4BY800
Type
Size
170M3416
1
170M3416
1
170M4410
1
170M5408
2
170M5410
2
170M6410
3
170M6411
3
67).
NEC type
UL
class
T
0124A-4
T
0156A-4
T
0180A-4
T
0240A-4
T
0260A-4
T
0361A-4
T
0414A-4
T
L
L