58 Guidelines for planning the electrical installation
This table shows the requirements when a non-ABB motor is in use.
Motor
Nominal AC supply
type
voltage
Random-
U
≤ 420 V
N
wound
and form-
420 V < U
≤ 500 V
N
wound
500 V < U
≤ 600 V
N
600 V < U
≤ 690 V
N
1)
If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term resistor
braking cycles, check with the motor manufacturer if additional output filters are needed in the applied drive
operation range.
The abbreviations used in the tables are defined below.
Abbr.
Definition
U
Nominal AC line voltage
N
Û
Peak line-to-line voltage at motor terminals which the motor insulation must withstand
LL
P
Motor nominal power
N
du/dt
du/dt filter at the output of the drive
CMF
Common mode filter
N
N-end bearing: insulated motor non-drive end bearing
n.a.
Motors of this power range are not available as standard units. Consult the motor manufacturer.
Motor insula-
ABB du/dt and common mode filters, insulated N-end
tion system
motor bearings
P
< 100 kW
N
and frame
size <
IEC 315
P
< 134 hp
N
and frame
size <
NEMA 500
Standard:
-
Û
= 1300 V
LL
Standard:
+ du/dt
Û
= 1300 V
LL
or
Reinforced:
-
Û
= 1600 V,
LL
0.2 micro-
second rise
time
Reinforced:
+ du/dt
Û
= 1600 V
LL
or
Reinforced:
-
Û
= 1800 V
LL
Reinforced:
+ du/dt
Û
= 1800 V
LL
-
Reinforced:
Û
= 2000 V,
LL
0.3 micro-
second rise
1)
time
Requirement for
100 kW ≤ P
< 350
N
kW
or
frame size ≥ IEC 400
IEC 315 ≤ frame size
< IEC 400
134 hp ≤ P
< 469 hp
N
or
NEMA 500 ≤ frame
size ≤ NEMA 580
+ N or CMF
+ N + CMF
+ du/dt + (N or CMF)
+ N + du/dt + CMF
+ N or CMF
+ N + CMF
+ du/dt + (N or CMF)
+ N + du/dt + CMF
+ N or CMF
+ N + CMF
+ du/dt + N
+ N + du/dt + CMF
+ N + CMF
+ N + CMF
P
≥ 350 kW
N
or
P
≥ 469 hp
N
or
frame size >
NEMA 580