If ambient temperature is below +40 °C (+104 .°F), the derating can be reduced by 1.5%
for every 1 °C reduction in temperature. Curves with derating factors from 1.00 to 0.80 are
shown below. For a more accurate derating, use the DriveSize PC tool. A few altitude
derating curves are shown below.
Installation site altitude
4000 m
13123 ft
3500 m
11429 ft
3000 m
9842 ft
2500 m
8202 ft
2000 m
6562 ft
1500 m
4921 ft
1000 m
3300 ft
+20 °C
+68 °F

Deratings for special settings in the drive control program

If you change the minimum switching frequency with parameter 97.02 Minimum switching
frequency, multiply the output current given in
given in this table.
Frame size
R6
R7
R8
R9
R10
R11
R11
R11
* current derating for -0414A-4 and -0430A-4 at 35 C
Note:
+25 °C
+30 °C
+77 °F
+86 °F
1.5 kHz
2 kHz
1.00
0.97
1.00
0.98
1.00
0.96
1.00*
0.95*
1.00
0.92
1.00
0.92
1.00
0.92
1.00
0.92
0.80
0.85
0.90
0.95
1.00
+35 °C
+95 °F
Ratings (page 149)
by the coefficient value
4kHz
0.84
0.89
0.82
0.79*
0.78
0.78
0.78
0.78
Technical data 153
+40 °C
+104 °F
Ambient temperature
8 kHz
0.66
0.71
0.61
0.58*
0.58
0.58
0.58
0.58