Fuses

The tables list the fuses for protection against short-circuits in the input power
cable or drive. The operating time depends on the supply network impedance, and
the cross-sectional area and length of the supply cable.
Do not use fuses that have a higher current rating than specified in the table. You
can use fuses from other manufacturers, if they meet the ratings, and if the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the
table.

IEC fuses

Either fuse type can be used if it operates rapidly enough.

gG fuses

Make sure that the operating time of the fuse is less than 0.5 seconds. Obey the
local regulations.
Current multiplier with different switching frequencies
2 kHz
4 kHz
1
1
1
1
1
1
1
1
1
1
1
1
Technical data 109
8 kHz
1
0.6
1
0.6
1
0.6
1
0.6
1
0.6
1
0.6
1
0.6
1
0.7
1
0.7
1
0.7
1
0.7
1
0.7
12 kHz
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.5
0.6
0.5
0.5
0.5