Output Frequency Derating; Fuses (Iec); Gg Fuses - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

Frame
ACH580-
size
01-
R7
125A-6
R8
144A-6
R9
192A-6
R9
242A-6
R9
271A-6

Output frequency derating

Output frequency derating applies for ratings up to ACH580-01-106A-4 (R5). Inverter
output current is limited by the following factor k below 5 Hz absolute inverter output
frequency f_abs.
k = 2/3 + 1/3 · (f_abs / 5 Hz)

Fuses (IEC)

gG as well as uR or aR fuses for protection against short-circuit in the input power cable
or drive are listed below. Either fuse type can be used for frames R1...R9 if it operates
rapidly enough. The operating time depends on the supply network impedance and the
cross-sectional area and length of the supply cable.
Note 1: See also
Implementing short-circuit and thermal overload protection (page
Note 2: Fuses with higher current rating than the recommended ones must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.

gG fuses

Check on the fuse time-current curve to ensure the operating time of the fuse is below
0.5 seconds. Obey the local regulations.
ACH580-
Min.
01-
short-
circuit
1)
current
A
3-phase U n = 230 V
04A7-2
200
06A7-2
200
07A6-2
200
Nominal
Nominal output current (I 2 ) for the minimum switching fre-
output
I 2
1 kHz
A
A
125
125
144
144
192
192
242
242
271
271
Input
current
Nominal
current
A
A
4.7
25
6.7
25
7.6
25
quencies at 40 °C (+104 °F)
2 kHz
4 kHz
A
A
125
125
144
144
192
192
242
201
271
201
gG (IEC 60269)
I 2 t
Voltage
rating
A 2 s
V
2500
500
2500
500
2500
500
Technical data 253
8 kHz
12 kHz
A
A
83
63
95
72
127
96
160
121
179
136
ABB type
OFAF000H25
OFAF000H25
OFAF000H25
16 kHz
A
N/A
N/A
N/A
N/A
N/A
106).
IEC
60269
size
000
000
000