Data Format; Precautions On Creating Data Using A Personal Computer - YASKAWA MP920 User Manual

Machine controller
Table of Contents

Advertisement

7.7.3

Data Format

The following diagram shows the data format when the 10 words of data from holding regis-
ters 0 to 9 are read by the SFC09 Holding Register Read (Extended) command, which is one
of the Extended MEMOBUS commands.
MEMOBUS Command
8
000
Command Type
001
Identification No.
002
Destination channel
003
Source channel
004
Not used
005
Not used
006
Data length
007
008
Not used
009
Not used
00A
Not used
00B
Not used
00C
Length
00D
00E
MFC
00F
SFC
010
CPU No.
011
Not used
012
Reference No.
013
014
Number of registers
015
7.7.4

Precautions on Creating Data Using a Personal Computer

Using Personal Computer as a Master
MEMOBUS Command Data
• Set the identification number each time communications are performed, using the fol-
lowing data order: 0 00 → 00 ff → 0 00.
• Specify 0 for the destination channel.
• Specify 0 for the source channel.
• When the remote station has more than one CPU, set the CPU number as follows:
Bit
Note: Destination CPU No.: Specify the CPU number of the Machine Controller.
7.7 Connection with Devices Manufactured by Other Companies
0
0× 11
0×00
0×00
0×00
0×00
218 header
0×16 (L)
0×00
0×00
0×00
0×00
0×00
(L)
0×08
0×00
(H)
0×20
Extended
0×09
MEMOBUS
0×00
packet
0×00
(L)
0×00
(H)
0×00
(L)
0×0A
(H)
0×00
7
4 3
Dest. CPU No.
Source. CPU No.
Source CPU No.: Set to 0.
7-35
MEMOBUS Respones
8
0×19
000
Command Type
001
Identification No.
0×00
002
Destination channel
0×00
003
Sourece channel
0×00
004
Not used
0×00
005
Not used
0×28
006
Data length
0×00
007
0×00
008
Not used
0×00
009
Not used
0×00
00A
Not used
0×00
00B
Not used
0×1A
00C
Length
0×00
00D
0×20
00E
MFC
0×09
00F
SFC
0×00
010
CPU No.
0×00
011
Not used
0×0A
012
Number of references
0×00
013
014
Data (MW0)
015
016
Data (MW1)
017
026
Data (MW9)
027
0
0
(L)
(L)
(H)
(L)
(H)
(L)
(H)
(L)
(H)
7
(L)
(H)