Machine Controller
Transmission Parameter Settings
2. Local Station's IP Address
Enter the local station's IP address. Do not use the same IP address for another node in
the Ethernet system.
An address consists of 32 bits, as shown in the following diagram. A period (.) separates
each 8-bit segment of the address, and each segment is entered in decimal.
Most significant bit
11000000 10101000 00000001 00000001
• The range of data to be entered differs for each field of the IP address.
• Field No. 1: 0 to 255 (except 127)
• Field No. 2: 0 to 255
• Field No. 3: 0 to 255
• Field No. 4: 1 to 254
IP addresses 192.168.1.1 to 192.168.1.254 are recommended as private addresses. Check with the net-
INFO
work administrator.
3. Response Time (Response Check Monitoring Time)
Enter the time (0 to 255) that the CP-218 will wait for a response to be returned after
transmitting a command using a system function (the MSG-SND function). If a
response is not returned and a timeout occurs, the transmission will be retried, but only
for the number of times set in parameter 4.
The Count of Retry parameter will be invalid if 0 is set in the Response Time parame-
ter.
Enter 0 for the Response Time if the Count of Retry is set to 0 (and MEMOBUS is set in the Proto-
INFO
col Type column of the CP-218 Connection Parameter Window).
Line Number
MP920
01 to 08
Least significant bit
7-15
7.5 CP-218 Transmission Definitions
Field No. 4
Field No. 3
Field No. 2
Field No. 1