Advertisement

A.2.4

Inputs

EXECUTE (RECEIVE MESSAGE EXECUTION Command)
When EXECUTE turns ON, the message is received. This command must be remained ON
until COMPLETE (Processing Completed) or ERROR (Error Occurred) turns ON.
ABORT (RECEIVE MESSAGE ABORT Command)
The ABORT command aborts message reception. This takes precedence over EXECUTE
(RECEIVE MESSAGE EXECUTION command).
DEV-TYP (Communications Device Type)
DEV-TYP specifies the communications device type.
Device
215IF
217IF
218IF
Serial
SVB-01
PRO-TYP (Communications Protocol)
PRO-TYP specifies the communications protocol.
When transmitting messages with the MELSEC or OMRON protocol, specify MEMOBUS
protocol (=1). Protocol is converted by the communications device (217IF or 218IF).
• MEMOBUS: Setting = 1
• No-protocol 1: Setting = 2 (Data is sent or received in word units without using a proto-
• No-protocol 2: Setting = 3 (Data is sent or received in byte units without using a proto-
Note: For no-protocol transmissions, no response is received from the
CIR-NO (Line No.)
CIR-NO specifies the line number.
Device
215IF
217IF
218IF
Serial
Type Code
1
5
6
8
11
col.)
col.)
sender.
Line No.
1 to 8
1 to 24
1 to 8
1 or 2
A-19