Appendix A System Functions
A.2.3 Parameter Details
2. COMMAND
Code
Symbol
1
U_SEND
2
U_REC
3
ABORT
8
M_SEND
9
M_REC
C
MR_SEND
3. RESULT
Code
Symbol
1
SEND_OK
2
REC_OK
3
ABORT_OK
4
FMT_NG
5
SEQ_NG, or INIT_NG Command sequence error:
6
RESET_NG, or
O_RING_NG
7
REC_NG
4. PARAMETER
PARAMETER indicates one of the error codes shown in Table A.2. when RESULT is
set to 4 (FMT_NG). Otherwise, it indicates the address of the remote station.
Table A.2 Error Codes
Code
00
No errors.
01
Station address outside the allowable range
02
MEMOBUS response receiving time error
03
Retry count setting error
04
Cyclic area setting error
05
Message signal CPU number error
06
Message signal register number error
07
Message signal word count error
5. REQUEST
1 = Request
0 = Acceptance completion report
Meaning
General-purpose message sent.
General-purpose message received.
Aborted.
MEMOBUS command sent: Processing completed upon
receiving response.
MEMOBUS command received: Followed by the sending
response.
MEMOBUS response sent.
Sending has been completed normally.
Receiving has been completed normally.
Abort completed.
Parameter format error
The token has not been received yet.
The communications system has not been connected.
Reset state:
Out-of-ring. The token was not be received even after
the token monitor time had elapsed.
Data receive error (error detected by a lower-level pro-
gram)
Error
A-16
Meaning

Hide quick links: