Parameter
P-62
P100011294 E
Description
Configure C/O in-/TB-input.
The TB-inputs detects a voltage between 24 V and 230 V.
C/O in-/TB-input: As soon as a voltage is detected the mode of operation of the
wireless connection module is changed to cooling. If this wireless connection
module is addressed to other wireless connection modules, then this C/O signal
will be sent to the other wireless connection modules within 3 minutes. Please
note wiring diagram Fig. 34, page 45. Phase and neutral have to be connected
as defined in this diagram. Phase (L) and zero conductor (N) must not be
swapped.
TB-input for temperature monitoring: When the maximum supply water tempera-
ture is reached, an external safety limiter will switch off the pump and transfers
this signal to the wireless connection module. Due to a primary pump or natural
circulation it is possible that water further circulates through the heating loops.
ATTENTION
The TB-input may not be used as safety temperature limiter.
NOTE
A radio channel configured as by-pass will not close when TB-input is activated.
Factory settings: Option "2"
Options
0: TB-input is configured as temperature monitor. When the input is activated
then the pump will be switched off immediately and all actuators are closed.
When activated the red LED lights at the wireless connection module and the
warning symbol is shown at the display of the wireless room thermostat.
1: TB-input is configured as temperature monitor. When the input is activated
then the pump will be not be switched off, but all actuators are closed. When
activated the red LED lights at the wireless connection module and the warn-
ing symbol is shown at the display of the wireless room thermostat.
2: The "C/O in"-Input is configured as change-over for heating and cooling
and as additional C/O-input. When this input is activated, then the wireless
connection module switches to cooling. The C/O-output is active.
Operation
Press sensor button
Press sensor button
Select one of the following options:
Press sensor button
next parameter P-63.
Press sensor button
lected parameter.
User Manual Roth EnergyLogic Touchline/Wireless
. The display shows 0.
or
, to select option 0, 1, or 2.
, to save the changed settings. The display shows the
, to interrupt the procedure. The display shows the se-
Parameter descriptions
95

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EnergyLogic Touchline/wireless and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Related Products for Roth EnergyLogic Touchline/wireless

Table of Contents

Save PDF