Parameter
P-33
P-34
P100011294 E
Description
Set unit for temperature.
●
Factory settings: Option "0"
●
Options:
–
0: °C
–
1: F
Operation
►
Press sensor button
►
Press sensor button
►
Select one of the following options:
–
Press sensor button
next parameter P-34.
–
Press sensor button
lected parameter.
Set dead-zone for change-over between heating and cooling.
The dead-zone will be applied by the wireless connection module as soon as the
mode of operation changes over from heating to cooling and visa versa. The value
of the dead-zone will be added to the setpoint "heating". The dead-zone is incorpo-
rated in the displayed room temperature setpoint.
Calculation:
Setpoint "cooling" = Setpoint "heating" + dead-zone
Example:
Setpoint "heating" = 21°C (shown setpoint during heating)
Dead-zone = 2 K,
Result:
Setpoint "cooling" = 21 + 2 = 23°C. (shown setpoint during cooling)
NOTE
The value for the "dead-zone" may only be changed if the mode of operation is set
at "heating". If this value is set during "cooling", the value will be doubled!
●
Factory settings: Option "0"
●
Options:
–
0: 2 K
–
1: 4 K
–
2: 6 K
–
3: 0 K, dead-zone deactivated
Operation
►
Press sensor button
►
Press sensor button
►
Select one of the following options:
–
Press sensor button
next parameter P-35.
–
Press sensor button
lected parameter.
User Manual Roth EnergyLogic Touchline/Wireless
. The display shows 0.
or
, to select option 1.
, to save the changed settings. The display shows the
, to interrupt the procedure. The display shows the se-
. The display shows 0.
or
, to select option 1, 2, or 3.
, to save the changed settings. The display shows the
, to interrupt the procedure. The display shows the se-