Variable Selector 1 Source 2; Variable Selector 1 Mode; Variable Selector 1 Destination; Variable Selector 1 Output/Variable Selector 1 Source 1 Scaling - Emerson Unidrive M200 Parameter Reference Manual

Open-loop mode
Hide thumbs Also See for Unidrive M200:
Table of Contents

Advertisement

Variable Selector 1 Mode

Variable Selector 1 Output (12.012)
(12.010)
0: Input 1
Input 1
1: Input 2
Input 2
2: Add
Input 1 + Input 2
3: Subtract
Input 1 - Input 2
4: Multiply
(Input 1 x Input 2) / 100.00%
5: Divide
(Input 1 x 100.00%) / Input 2
6: Time Const
Input 1 / (1 + τs) where τ is Variable Selector 1 Control (12.015) in seconds
Input 1 is an input to a linear ramp function where the time to ramp from 0.00% to 100.00% of the input parameter
7: Ramp
range is defined by Variable Selector 1 Control (12.015) in seconds. e.g. if the input parameter is at 50% of its range,
the output value will reach 50% in 50% of the time set in Variable Selector 1 Control (12.015)
8: Modulus
| Input 1 |
If Variable Selector 1 Control (12.015) = 0.02 then Output = Input
9: Powers
Else if Variable Selector 1 Control (12.015) = 0.03 then Output = Input
Else Output = Input 1
Parameter

12.009 Variable Selector 1 Source 2

Short description
Defines the 2nd source parameter for variable selector 1
Mode
Open‑loop
Minimum
0.000
Default
0.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW, PT, BU
See Variable Selector 1 Source 1 (12.008).
Parameter
12.010 Variable Selector 1 Mode
Short description
Defines the mode for variable selector
Mode
Open‑loop
Minimum
0
Default
0
Type
8 Bit User Save
Display Format
Standard
Coding
RW, TE
Value
Text
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
See Variable Selector 1 Source 1 (12.008).
Parameter

12.011 Variable Selector 1 Destination

Short description
Defines the destination parameter for variable selector 1
Mode
Open‑loop
Minimum
0.000
Default
0.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW, DE, PT, BU
See Variable Selector 1 Source 1 (12.008).
Parameter
12.012 Variable Selector 1 Output
Short description
Displays the output of variable selector 1
Mode
Open‑loop
Minimum
-100.00
Default
Type
16 Bit Volatile
Display Format
Standard
Coding
RO, ND, NC, PT
See Variable Selector 1 Source 1 (12.008).
Parameter
12.013 Variable Selector 1 Source 1 Scaling
Short description
Defines the scaling for the 1st input for variable selector 1
Mode
Open‑loop
Minimum
-4.000
Default
1.000
Type
16 Bit User Save
Display Format
Standard
Coding
RW
See Variable Selector 1 Source 1 (12.008).
194
2
/ 100.00%
3
/ (100.00%)
Maximum
30.999
Units
Update Rate
Drive reset read
Decimal Places
3
Maximum
9
Units
Update Rate
Background read
Decimal Places
0
Maximum
30.999
Units
Update Rate
Drive reset read
Decimal Places
3
Maximum
100.00
Units
%
Update Rate
4ms write
Decimal Places
2
Maximum
4.000
Units
Update Rate
4ms read
Decimal Places
3
2
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents