Ambient Conditions - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

316 Technical data

Ambient conditions

Installation site altitude 0 to 2000 m (6600 ft)
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
Sinusoidal vibration
(IEC 60721-3-3)
Shock
(IEC 60068-2-27,
ISTA 1A)
Free fall
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Environmental limits for the drive are given below. The drive is to be
used in a heated indoor controlled environment.
Operation
installed for
stationary use
above sea level
(above 1000 m
[3300 ft], see section
on page
Derating
309)
-10 to +50 °C (14 to
122 °F). No frost
allowed. See section
on page
Derating
309.
0 to 95%
No condensation allowed. Maximum allowed relative humidity is
60% in the presence of corrosive gases.
No conductive dust allowed.
According to
IEC 60721-3-3,
chemical gases:
Class 3C2
solid particles: Class
3S2.
The drive must be
installed in clean air
according to
enclosure
classification. Cooling
air must be clean,
free from corrosive
materials and
electrically conductive
dust.
Tested according to
IEC 60721-3-3,
mechanical
conditions: Class 3M4
2...9 Hz, 3.0 mm
(0.12 in)
2
9...200 Hz, 10 m/s
2
(33 ft/s
)
-
Not allowed
Storage
in the protective
package
-
-40 to +70 °C (-40 to
+158 °F)
Max. 95%
According to
IEC 60721-3-1,
chemical gases:
Class 1C2
solid particles: Class
1S2
-
According to ISTA 1A.
2
Max. 100 m/s
2
(330 ft/s
), 11 ms.
76 cm (30 in)
Transportation
in the protective
package
-
-40 to +70 °C (-40 to
+158 °F)
Max. 95%
According to
IEC 60721-3-2,
chemical gases:
Class 2C2
solid particles: Class
2S2
-
According to ISTA 1A.
2
Max. 100 m/s
2
(330 ft/s
), 11 ms.
76 cm (30 in)