Fieldbus References; Reference Selection And Correction - ABB ACS310 User Manual

Hide thumbs Also See for ACS310:
Table of Contents

Advertisement

Parameter
Setting for
fieldbus
control
FAULT
COMM
1604
RESET SEL
LOCAL
COMM
1606
LOCK
PARAM
DONE;
1607
SAVE
SAVE
START
COMM
1608
ENABLE 1
START
COMM
1609
ENABLE 2
LIMITS
ACC/DEC
COMM
2201
1/2 SEL
RAMP
COMM
2209
INPUT 0
COMMUNICATION FAULT FUNCTIONS
COMM
NOT SEL
3018
FAULT FUNC
FAULT
CONST SP
7
LAST
SPEED
0.1...60.0 s Defines the time between
COMM
3019
FAULT TIME
PID CONTROLLER REFERENCE SIGNAL SOURCE SELECTION
COMM
4010/4110/4210
SET POINT SEL
COMM+AI1
COMM*AI1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Fieldbus control with embedded fieldbus 269
Function/Information
Enables fault reset through fieldbus
FB CMD WORD 1 bit 4 (with
0301
ABB drives profile
5319
bit 7).
Local control mode lock signal
through
FB CMD WORD 1 bit
0301
14
Saves parameter value changes
(including those made through
fieldbus control) to permanent
memory.
Inverted Start Enable 1 (Start Disable)
through
FB CMD WORD 2 bit
0302
18
Inverted Start Enable 2 (Start Disable)
through
FB CMD WORD 2 bit
0302
19
ACC/DEC ramp pair selection
through
FB CMD WORD 1 bit
0301
10
Ramp input to zero through
CMD WORD 1 bit 13 (with ABB driv es
profile
EFB PAR 19 bit 6)
5319
Determines drive action in case
fieldbus communication is lost.
communication loss detection and the
action selected with parameter
COMM FAULT FUNC.
PID control reference (REF2)
Modbus register
address
40001 bit 7 40031 bit 4
EFB PAR 19
-
41607
-
-
ABB DRV
-
FB
40001 bit 6 40031 bit
0301
ABB DRV
43018
43019
3018
ABB DRV
40003 for REF2
40031 bit
14
40032 bit
18
40032 bit
19
DCU
40031 bit
10
13
DCU
DCU