138 Program features

Example

The time scheme below visualizes the operation of the sleep function.
Reference
Sleep boost step (4031)
Selected process
actual value
Wake-up level deviation
(4025)
Output frequency
= Sleep delay (4024)
t
sd
Sleep level
(4023)
Sleep function for a PID controlled pressure boost pump (when parameter 4022 is set
to INTERNAL): The water consumption falls at night. As a consequence, the PID
process controller decreases the motor speed. However, due to natural losses in the
pipes and the low efficiency of the centrifugal pump at low speeds, the motor does not
stop but keeps rotating. The sleep function detects the slow rotation, and stops the
unnecessary pumping after the sleep delay has passed. The drive shifts into sleep
mode, still monitoring the pressure. The pumping restarts when the pressure falls
under the allowed minimum level and the wake-up delay has passed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
t < t
t
sd
sd
Sleep boost time (4030)
Wake-up delay
(4026)
Control panel:
PID
SLEEP
Stop
Time
Time
Time
Start